Interlogix Monitor XL Hardware Guide Bedienungsanleitung Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 66
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
22-0375 rev1.1 Monitor ISM/xL™ Hardware Guide 23
SN#:1B3414 Edit
Save Pxxx2
This screen will then
display:
SN#:1B3414: This is
the Serial Number of the sensor that was enrolled
into this input number.
Pressing the keypad right arrow button will display
the
SVN:0 TMP: IN: screen for editing. The
Del‘ button can also be pressed to remove the
sensor and another sensor could be programmed
for this input number if desired.
Equipment/Pseudo Point Selections for Wireless V2
Module Trouble (E011), ensure this is set to detect:
Module Bus connection to V2 module failure.
V2 module failure.
V2 module has not received any sensor signal for X
amount of time (
AllSVN).
Module Battery Low (E012), ensure this is set so
‘Senor Low Battery’ will be detected.
Module Program Edit (E013) can be optionally set to
detect when the sensor settings have been changed.
This alert will not re-set until there have not been any
further program changes for one hour.
LCD Keypad Status
Enter ‘Status’ at the system’s LCD keypad.
Press the keypad’s right arrow key until App
(Application Module) displays. Press the keypad
button under it.
When Wireless2 or WL2 displays, press the button
under
Yes.
Keypad left and right arrow keys can be pressed to
scroll through the input numbers and V2 module
conditions.
Input Number Status
The input number range associated with the V2 will
display and the input’s condition e.g.
009Ok.
It can also display the following for an input:
NoSvn‘ No Supervision. A sensor supervision signal
failure. The input will appear in point status as a
tamper.
Lobat‘ Low senor battery. This will generate a
module or pod low battery alert. If the sensor’s
battery was replaced, the sensor’s reset button on
its printed circuit board must be pressed.
Not Enrolled‘ A sensor is not programmed to
this input. The input will appear in point status as a
tamper. Delete the input if it will not be used.
NoRcv‘ No Receiver detected. V2 module
malfunction.
PtTmp‘ Input sensor tamper. The input will appear
in point status as a tamper.
V2 Module Status
After scrolling through all the V2 input conditions, the
condition of the V2 module will display: e.g.
PodOk.
It can also display the following for a module:
NoSvn‘ The V2 module is not communicating on the
module bus.
NoSen‘ The V2 module has not received
communication from its sensors, based on the
supervision delay period set for the V2 module
(
AllSVN).
Module Status will display the V2 module in tamper
for either of these conditions.
V2 Test Menus
Log on to the system LCD keypad as a Service
User.
SelectTest‘ from the Menu and App WL2 or
Wireless2.
Check (X.Xx)
Signal Scan
This screen will display:
(X.Xx) indicates the V2
firmware version number.
Signal‘ selects a sensor signal strength menu.
xxx < > Si > 3 OK
Signal 014 of 21
Pressing ‘Signal‘ will
display this screen:
xxx represents an
input sensor number on the V2 module.
< > keypad left and right arrow keys can be pressed
to scroll through the input numbers.
Si(gnal) > 3 OK is an example of the V2 receiver
getting an adequate signal strength from the sensor.
xxx < > Si > 4 Weak
Signal 001 of 21
This screen is an example
of the V2 receiver getting
an inadequate signal from
the sensor.
The second line in both screens displays the actual
signal strength measured on a scale of 000 to 021
(maximum).
If a sensor has not been enrolled in an input
number,
Not Enrolled will display on the top line.
Scan‘ selects an RF scanning menu.
When ‘Scan’ is pressed the screen will display
Waiting...’ to receive an RF transmission from
any sensor. NOTE: if this screen never changes, it is
possible the V2 module is not working properly.
SN#:1B3414 LEARN
AA BB
If this screen displays
when a signal is received,
it is from a sensor that has
not been enrolled in the system, indicated by
LEARN. SN#:1B3414 is the sensor’s unique serial
number.
SN#:1B3414*P#xxx
AA BB
If this screen displays
when a signal is received,
it is from a sensor that is
enrolled in the system, indicated by P#xxx where
xxx is the input number.
Either an asterisk or a blank will display after a
sensor’s serial number as it toggles every time a
transmission from a different sensor is received.
In either screen, ‘AA BB‘ is changing data that can
be ignored. It is for internal Engineering use only.
Seitenansicht 26