TruPortal Software User Guide 31
Configuring Devices
Note: The Tamper option controls the tamper input point only, not the Door Contact, Request
to Exit, or Aux Input points. Also, this option will not appear on the System
Administration > Devices page if a door is connected to an IPSDC, which does not
support reader tamper input.
Aux Input
Note: This field will not appear on the System Administration > Devices page if a door is
connected to an IPSDC, which does not support auxiliary input/output types. Refer to
the IP-based Single Door Controller Quick Reference to learn about modifying jumper
settings for input types.
None
Indicates the input is not used and not monitored.
Extended RTE
Intended for use only with the Door Opener option selected for Aux Relay.
Mag Lock Bond Sense
Intended for doors that use a magnetic lock instead of a door strike. This detects the output from
the magnetic lock indicating the door has bonded to the magnet. The System will not activate the
magnet until the door bond sensor sends a signal indicating the door has made contact with the
magnet and the door contact sensor indicates the door is closed. This prevents the magnet from
activating prematurely and causing the door to slam closed.
If “Timed Unlock” is selected for Door Strike Mode, then the magnet will remain inactive until
that time has expired. However, it will still not activate until the magnetic bond sensor and door
contact sensor signals are received indicating the door is closed and bonded to the magnet.
Aux Relay
Note: This field will not appear on the System Administration > Devices page if a door is
connected to an IPSDC, which does not support auxiliary input/output types. Refer to
the IP-Based Single Door Controller Quick Reference to learn about modifying jumper
settings for input types.
None
Indicates the relay is not used and not energized.
Door Held/Forced
A typical use for this option is to have the relay trigger some physical alarm, such as a siren or
light, whenever the door is held or forced open.
Door Opener
Typically used with a door configured with a single reader for entry and a manual release wired
for RTE, and a push button for an Extended RTE automatic opener. The RTE input unlocks the
door for the duration that the manual release is active so that someone can exit normally. The
Aux input (Extended RTE) activates the Aux Relay for the specified Aux Relay On Time. This
relay output activates a door opener that automatically unlocks and opens the door for a person
needing assistance.
This setting only makes sense if Aux Input is configured for Extended RTE.