Concord 4 Installation Guide 3
Max. wire
length to
panel
22 ga.: 110 ft.
18 ga.: 260 ft.
Tw o-wire smoke detectors
(429AT, 429C, 429CT,
521B, 521BXT, 521NCSXT
22 ga.: 330 ft.
18 ga.: 330 ft.
Tw o-wire smoke detectors
(system sensor 2400,
2400TH)
22 ga.: 330 ft.
18ga.: 330 ft.
Hardw ired interior siren (13-
949)
22 ga.: 750 ft.
18 ga.: 1,500 ft.
Piezo dynamic exterior siren
(13-060)
22 ga.: 750 ft.
18 ga.: 1,500 ft.
Speaker siren (60-528 or
13-060)
1
Maximum current draw for the SnapCards does not include the load
w hich may be applied to their auxiliary DC supply.
Note: When installing SuperBus 2000 RF receiver
modules, the antenna tamper feature must be set to off.
Table 4 below describes the total system wire lengths
allowed for all SuperBus 2000 devices when installing
systems using unshielded or shielded cable. The
maximum wire length for individual devices is shown
instable below.
Table 4: Total system wire lengths
After determining panel location, run all necessary wires
to that location using the guidelines in Table.
Table 5: Device wire requirements
2-conductor, 18-gauge, 25 ft. max.
Single conductor, 16-gauge solid, 25 ft. max.
2- or 4-conductor, 22-gauge, 1,000 ft. max.
2- or 4-conductor, 18-gauge, 2,500 ft. max.
(based on 30 ohms max. loop resistance
including device)
2-conductor, 18-gauge, 100 ft. max.
4-conductor, 22- or 18-gauge
Interrogator 200 AVM
pow er and microphone
4-conductor, 22-gauge, shielded
Tw o-wire smoke
detectors
2-conductor, 22-gauge, 330 ft. max.
2-conductor, 18-gauge, 830 ft. max.
Mounting the panel
Mount the panel to the wall or wall studs.
Caution: Make sure you are free of static electricity
whenever you work on the panel with the cover open. To
discharge any static, first touch the metal panel chassis,
and then stay in contact with the chassis when touching
the circuit board. We recommend using a grounding
strap.
To mount the panel:
1. Remove the panel door and remove the necessary
wiring knockouts. Be careful not to damage the
circuit board.
2. Feed all wires through wiring knockouts and place
the panel in position against the wall.
3. Level the panel and mark the top and bottom
mounting holes.
4. Install anchors where studs are not present.
5. Partially insert screws into the two top mounting hole
locations, then hang the panel on the two screws.
6. Recheck for level, insert the two lower screws, and
tighten all four mounting screws.
Figure 1 below shows the main component locations.
Figure 1: Panel components
EPROM
Antennas
Mounting hole
Mounting hole
Mounting holes
Snapcard
connector
Terminal strip
Programming
touchpad
header
Battery
terminals