ANSI/SIA CP-01 requirements
CP-01 feature descriptions and specifications are listed in Table 9 below. The following are requirements for compliance with
ANSI/SIA CP-01 standards.
Note: Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.
• Minimum system requirements:
• One control panel
• Two keypads
• Do not enable remote arming in SIA classified installations.
• Off premise transmission must be in the SIA format.
• Do not exceed 1 minute for the abort window and entry delay.
Note: A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station.
Table 9: CP-01 feature descriptions and specifications
CP-O1 feature description Feature description as shown in
manual
Program
location
Seg/opt Default CP-01required setting
Exit 1 delay 24 2 60 45 to 240 seconds Exit time
Exit 2 delay 24 4 60 45 to 240 seconds
Progress annunciation /
disable - for silent exit
Silent keypad option 93
a
2 All annunciators enabled Allowed (individual
keypads may be disabled)
Exit time restart (reexit) This feature is not programmable in the panel. Enabled
Auto stay arm on unvacated
premises
Auto bypass 23 1/3 Enabled Enabled
Exit time and progress
annunciation/disable for
remote arm
This feature is not programmable in the panel. Exit time and progress are always
enabled.
Enabled (disabled for
remote arming)
Entry 1 delay 24 1 30 30 to 240 seconds Entry delays
b
Entry 2 delay 24 3 30 30 to 240 seconds
Abort window - for nonfire
zones
Dialer delay 40 8 30 Enabled (may be disabled
by zone/zone type, but no
cancel reports will be sent)
Abort window time - for
nonfire zones
b
Dialer delay 40 8 30 15 to 45 seconds
Abort annunciation This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.
Enabled
Cancel annunciation Cancel 23 3/6 Enabled Enabled
Duress feature Duress 44 Disabled Disabled
Two trips on cross zone 37 5/4 Disabled Required
Keypad sounds on cross zone trip 39 5 Disabled
Cross zoning
Zone type characteristic 111 3/4 Disabled
Programmable cross zoning
time
Cross zone time 40 6 5 minutes Allowed
Swinger shutdown Swinger shutdown count 38 n/a n/a For all nonfire zones, shut
down at 1 to 2 trips
Swinger shutdown disable Swinger shutdown count 38 n/a Enabled for 1 trip Allowed
Fire alarm verification Fire alarm verification time 40 9 Enabled for 1 trip Required (depends on
panel and sensors)
10 NX-8V2 Control Panel Installation Instructions