NX-1710E Addendum (February 9, 2005 -- cksum 9B12)
Only the modified locations are reflected in this Addendum.
The NX-1710E has been upgraded to operate with the following 2-wire Wiegand bus interface. Readers must be able to “speak” Wiegand. The following are supported
Weigand formats by default:
26-bit standard Weigand
27-bit Tecom ASC
35-bit HID Corporate 1000
37-bit HID 10304
40-bit with facility code (Casi Rusco 4001)
40-bit without facility code (Casi Rusco 4002)
LOCATION 1 READER “B” SCAN FUNCTIONS & OPTIONS
Segment 3 Reader Options:
LED5 = “On” if LED to extinguish after 2 minutes without a scan. (Note: This option doesn’t disable the flashing green LED during card programming.)
L
OCATION 3 PROGRAMMING THE OPTIONS AND DOOR CONTROL PARTITIONS
Segment 2 Door Options
LED8 = “On” if relay operates normally during off-schedule (outside regular operating hours).
Segment 5 Weigand Format Enables:
LED1 - "On" if Weigand Format #1 is enabled. (Default is “On”)
LED2 - "On" if Weigand Format #2 is enabled. (Default is “On”)
LED3 - "On" if Weigand Format #3 is enabled. (Default is “On”)
LED4 - "On" if Weigand Format #4 is enabled. (Default is “On”)
LED5 - "On" if Weigand Format #5 is enabled. (Default is “On”)
LED6 - "On" if Weigand Format #6 is enabled.
LED7 - "On" if Weigand Format #7 is enabled.
LED8 - "On" if Weigand Format #8 is enabled.
L
OCATION 44 CODE ENTRY LOGGING PARTITION
(2 segments of numerical data) This location programs the partition that is logged with the Code Entry message and sent when the following conditions are met:
An RTE scan function is selected (Location 0, Segment 1/2, Option 8); and
“RTE from a scanned card is to be logged as Code Entry” is enabled (Location 3, Segment 1, Option 5).
Entering a 0 (zero) will send the lowest valid partition of the reader. Entering 1-16 will send the entered value as the partition. (Default is 0.)
Segment 1 Code Entry Logging Partition for Reader “A”
Segment 2 Code Entry Logging Partition for Reader “B”
USER-DEFINABLE FORMATS
The following locations are considered to be advanced programming and should ONLY be used by installers with a thorough
understanding of Weigand Formats. Do not attempt to program these locations if you are not familiar with Weigand packets.
L
OCATION 45 WEIGAND FORMAT 1 (STANDARD 26 BIT) – DIGITS & BITS
(5 segments of decimal data) This is the first location used to program the Weigand Format 1. (Loc 45-57)
Segment 1 Number of digits in Facility Code
Segment 2 Number of digits in Badge Number
Segment 3 Number of bits in Facility Code
Segment 4 Number of bits in Badge Number
Segment 5 Total number of bits in complete format (including parity bits)
L
OCATION 46 WEIGAND FORMAT 1 – BIT DESCRIPTORS (BITS 1-32)
(32 segments of hex data) This location contains the descriptors for bits 1 – 32 of Weigand Format 1. The available options are: 0=Always Zero; 1=Always One; B=Badge
number; D=Parity bit; E=End of format; F=Facility Code bit. Segment 1 = Bit Descriptor 1; Segment 32 = Bit Descriptor 32.
L
OCATION 47 WEIGAND FORMAT 1 – BIT DESCRIPTORS (BITS 33-64)
(32 segments of hex data) This location contains the descriptors for bits 33 – 64 of Weigand Format 1. The available options are: 0=Always Zero; 1=Always One; B=Badge
number; D=Parity bit; E=End of format; F=Facility Code bit. Segment 1 = Bit Descriptor 33; Segment 32 = Bit Descriptor 64.
L
OCATION 48 WEIGAND FORMAT 1 – PARITY TYPE 1
(1 segment of decimal data) This location programs the Partity Type 1 for Weigand Format 1. Available options for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.
Factory default is 1.
L
OCATION 49 WEIGAND FORMAT 1 – PARITY MASK 1
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity bits. It is used in conjunction with Location 48 (Parity Type 1). The factory
default is:
Seg 1 Seg 2 Seg 3 Seg 4 Seg 5 Seg 6 Seg 7 Seg 8
12345678 12345678 12345678 ------78 -------- -------- -------- --------
L
OCATION 50 WEIGAND FORMAT 1 – PARITY TYPE 2
(1 segment of decimal data) This location programs the Partity Type 2 for Weigand Format 1. Available options for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.
Factory default is 2.
L
OCATION 51 WEIGAND FORMAT 1 – PARITY MASK 2
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity bits. It is used in conjunction with Location 50 (Parity Type 2). The factory
default is:
Seg 1 Seg 2 Seg 3 Seg 4 Seg 5 Seg 6 Seg 7 Seg 8
12345678 ---45678 -------- -------- -------- -------- -------- --------
L
OCATION 52 WEIGAND FORMAT 1 – PARITY TYPE 3
(1 segment of decimal data) This location programs the Partity Type 3 for Weigand Format 1. Available options for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.
Factory default is 0.
L
OCATION 53 WEIGAND FORMAT 1 – PARITY MASK 3
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity bits. It is used in conjunction with Location 52 (Parity Type 3). The factory
default is:
Seg 1 Seg 2 Seg 3 Seg 4 Seg 5 Seg 6 Seg 7 Seg 8
-------- -------- -------- -------- -------- -------- -------- --------
Seitenansicht 0
1 2 3 4 5 6 7 8 9

Inhaltsverzeichnis

Seite 1

NX-1710E Addendum (February 9, 2005 -- cksum 9B12) Only the modified locations are reflected in this Addendum. The NX-1710E has been upgraded to oper

Seite 2

 Tip: Defaults are shown in bold italics.LOCATION 54 WEIGAND FORMAT 1 – PARITY TYPE 4 (1 segment of decimal data) This location programs the Part

Seite 3

5 Bit 37 Descriptor E 21 Bit 53 Descriptor E 6 Bit 38 Descriptor E 22 Bit 54 Descriptor E 7 Bit 39 Descriptor E 23 Bit 55 Des

Seite 4

14 Bit 46 Descriptor E 30 Bit 62 Descriptor E 15 Bit 47 Descriptor E 31 Bit 63 Descriptor E 16 Bit 48 Descriptor E 32 Bit 64

Seite 5

3 Parity Mask 3 12345678 7 Parity Mask 7 -------- 4 Parity Mask 4 12345678 8 Parity Mask 8 -------- LOCATION 76 – WIEGAND FORMA

Seite 6

LOCATION 91 – WIEGAND FORMAT 4 (PARITY TYPE 3) 0=No Parity; 1=Odd Parity; 2=Even Parity 1 Parity Type 3 0 LOCATION 92 – WIEGAND FORMAT 4 (P

Seite 7

LOCATION 107 – WIEGAND FORMAT 5 (PARITY MASK 4) 1 Parity Mask 1 -------- 5 Parity Mask 5 -------- 2 Parity Mask 2 -------- 6 Parity M

Seite 8

LOCATION 122 – WIEGAND FORMAT 6 (PARITY MASK 5) 1 Parity Mask 1 -------- 5 Parity Mask 5 -------- 2 Parity Mask 2 -------- 6 Parity

Seite 9 - GLADEWATER, TEXAS 75647

WEIGAND FORMAT 8 LOCATION 136 – WIEGAND FORMAT 8 (DIGITS & BITS) (DECIMAL DATA) DESCRIPTION DEFAULT DATA 1 Number of Digits in Facility Code

Kommentare zu diesen Handbüchern